Metadatos de indexación

Características de las fallas en alimentadores de 13,8 kV del sistema soterrado de La Habana; Characteristic of 13,8 kV feeders faults of the Havana underground system


 
Dublin Core Elementos de metadatos PKP Metadatos para el documento
 
1. Título Título del documento Características de las fallas en alimentadores de 13,8 kV del sistema soterrado de La Habana; Characteristic of 13,8 kV feeders faults of the Havana underground system
 
2. Creador/a Nombre de autor/a, institución, país Boris Alba Valle; Cuba
 
2. Creador/a Nombre de autor/a, institución, país José Ángel Martínez Barbado; Cuba
 
3. Materia Disciplina(s) Ingeniería Eléctrica
 
3. Materia Palabra/s clave cantidad de fallas; herramientas estadísticas digitales; alimentadores de 13,8 kV; medidas objetivas; faults quantity; digital statistical tools; 13,8 kV feeders; objective measures
 
3. Materia Clasificación por materias TRABAJOS TEÓRICOS EXPERIMENTALES
 
4. Descripción Resumen

El sistema soterrado de La Habana enfrenta problemas de continuas fallas en sus alimentadores de 13,8 kV.
En este trabajo se determinan las características de estas averías, en el período comprendido entre los años
2007 y 2009, y se proponen algunas medidas objetivas con el fin de contribuir a su disminución. La investigación
se basó fundamentalmente en el estudio de la base de datos de los alimentadores de 13,8 kV proporcionada por
el departamento técnico de la Unidad Empresarial Básica (UEB) Soterrada y en el uso de herramientas
estadísticas digitales. Como resultado se pudo constatar que las fallas son más frecuentes en los alimentadores
de la subestación de Tallapiedra producto de la humedad en cables y empalmes con aislamiento de PILC (papel
impregnado en aceite y con cubierta de plomo), dispuestos por tierra muerta. Finalmente, las medidas
propuestas tuvieron un impacto positivo en la disminución de estas fallas, en un período inferior a un año.

 

 

The Havana underground system has problems of continuous faults in their 13,8 kV feeders. In this article the
characteristics of these mishaps in the period of 2007 to 2009 are determined and purpose some objective
measurements with the end of contributing to their decrease. The investigation was fundamentally based on the
study of the 13,8 kV feeders database proportioned by the technical department of the Underground Basic
Managerial Unit (UEB) and the use of digital statistical tools. As a result, it was verified that the faults occur with
more frequency in the Tallapiedra substation feeders, due to the humidity in cables and connections with PILC
isolation (impregnated in oil and lead covered paper), prepared for undergrounding directly in the earth. Finally,
the proposed measures had a positive impact in the decrease of these faults, in a period less than to a year.

 
5. Editorial Institución organizadora, ubicación Universidad Tecnológica de La Habana "José Antonio Echeverría" (Cujae)
 
6. Colaborador/a Patrocinador(es)
 
7. Fecha (DD-MM-AAAA) 2011-06-09
 
8. Tipo Estado y género Artículo revisado por pares
 
8. Tipo Tipo
 
9. Formato Formato de archivo PDF
 
10. Identificador Identificador uniforme de recursos http://rie.cujae.edu.cu/index.php/RIE/article/view/293
 
11. Fuente Título; vol., núm. (año) Ingeniería Energética; Vol. 32, Núm. 2 (2011): Ingeniería Energética
 
12. Idioma Español=es es
 
13. Relación Archivos complementarios
 
14. Cobertura Localización geoespacial, periodo cronológico, muestra de investigación (sexo, edad, etc.)
 
15. Derechos Derechos de autor/a y permisos Copyright (c)